Model | Press Side | Range (bar) | Differential (bar) | Factory Setting (bar) | Max Opareting Pressure (bar) |
|||
Min | Max | Min | Max | Off | On | |||
SFC-F5832 | Low Side | -0.2 | 0.7 | 4 | 4 | 2 | 20 | |
High Side | 8 | Fixed 4 | 20 | 15 | 35 | |||
SFC-F5832MM | Low Side | -0.2 | 0.7 | 4 | 4 | 2 | 20 | |
High Side | 8 | Fixed 4 | 20 | Manual Reset | 35 | |||
SFC-F5832HLM | Low Side | -0.2 | Fixed 4 | 3 | Manual Reset | 20 | ||
High Side | 8 | Fixed 4 | 20 | Manual Reset | 35 |